SEL-387A

SEL-387A

Current Differential and Overcurrent Relay
  • The SEL-387A is an economical and efficient solution designed for the protection, monitoring, and control of two-winding power transformers. It inherits the high-performance protection features of the SEL-387 but is optimized for two-winding applications to provide superior cost-effectiveness. Combining differential and overcurrent protection, it can be flexibly applied to various power apparatus, including transformers, buses, generators, and reactors.

Key Features

  • Two-Winding Differential Protection (87)

    Provides single- or dual-slope percentage restrained differential characteristics to maintain stability and prevent misoperation during through-fault conditions.
  • Harmonic Control and Security

    Includes 2nd, 4th, and 5th harmonic blocking to prevent false trips during transformer energization (inrush) or overexcitation, supplemented by DC element detection.
  • Automatic Compensation

    Performs internal phase angle and CT ratio compensation, allowing for easy installation without the need for external correction CTs.
  • Comprehensive Overcurrent Protection

    Provides multi-layered backup protection using phase, negative-sequence, and residual overcurrent elements.
  • Optional Restricted Earth Fault (REF)

    Supports the addition of two REF elements for sensitive detection of ground faults in wye-connected transformers.
  • SELogic Control Equations

    Allows users to configure custom protection and control logic using variables, timers, latch bits, and more.

Convenience features

  • Advanced Asset Monitoring

    Through-Fault Monitor: Records the accumulated stress from through-faults to help manage equipment lifespan and optimize maintenance schedules.
    Temperature Monitoring: Integrates with the SEL-2600 RTD Module for real-time monitoring of critical operating temperatures.
    Condition Monitoring: Includes standard breaker contact wear monitoring (Breaker Monitor) and station battery voltage monitoring.
  • Event Analysis and Recording

    Features high-resolution oscillographic event reports and Sequential Events Recorder (SER) for rapid and accurate root-cause analysis of disturbances.
  • Flexible Communication Interface

    Equipped with four independent serial ports (one front/two rear EIA-232, one rear EIA-485) for simultaneous connection to multiple supervisory systems.
  • Optimized Field Operations

    Provides an advanced local operator interface with programmable text display points and local control elements for intuitive monitoring and operation.