SEL-700BT

SEL-700BT

Motor Bus Transfer Relay
  • The SEL-700BT is a comprehensive Motor Bus Transfer (MBT) protection relay designed for critical process environments. When a fault occurs on the primary power source, it provides automatic and manual transfer of critical loads to an auxiliary feeder. This ensures continuous process operation without requiring a "cold start" of motors after they have stopped.

Key Features

  • Four Transfer Methods

    Supports Fast, In-phase, Residual Voltage, and Fixed-time transfer methods to perform the most appropriate transfer based on real-time system conditions.
  • Flexible Transfer Modes

    Supports both Sequential and Simultaneous transfer modes to accommodate various breaker configurations and operational requirements.
  • Comprehensive Protection Suite

    Provides robust primary and backup motor bus protection, including current, voltage, frequency, distance, loss-of-potential, and out-of-step elements.
  • Latest Sensor Technology Compatibility

    Supports Low-Energy Analog (LEA) voltage sensors, Rogowski coils, and Low-Power Current Transformer (LPCT) inputs, making it ideal for modern digital substation and switchgear designs.
  • Combined Winding Overcurrent Protection

    Includes a combined winding overcurrent element for more precise and reliable overload and fault protection.
  • Enhanced Network Reliability

    Supports Rapid Spanning Tree Protocol (RSTP) and Parallel Redundancy Protocol (PRP) to ensure uninterrupted data transmission and rapid recovery in the event of a network failure.

Convenience features

  • 5-Inch Color Touchscreen

    Features a large touchscreen HMI that allows users to intuitively monitor bay screens, metering values, and event reports, and operate the device locally.
  • Extensive Standard Protocols

    Supports a wide array of protocols, including IEC 61850 Edition 2, DNP3, Modbus TCP/RTU, EtherNet/IP, Telnet, and FTP, ensuring seamless integration with existing systems.
  • Precise Time Synchronization

    Supports IEEE 1588 PTP (Precision Time Protocol) to provide microsecond-level accuracy for event recording and system-wide synchronization.
  • Versatile I/O Scalability

    Offers hardware expansion options to meet specific field requirements, including serial communication cards, RTD inputs, analog inputs/outputs (AI/AO), and various digital I/O cards.
  • User-Friendly Software

    SEL configuration tools allow users to visually configure and manage complex bus transfer logic and protection settings.